Add emergency lighting (DT1) memory bank 208 and query helpers - #159
Conversation
1fa16e4 to
b045191
Compare
| emergency control gear in a single sequence. | ||
|
|
||
| Running it as a sequence ensures the required "ENABLE DEVICE TYPE 1" | ||
| command is sent before each application-extended command, so the gear |
There was a problem hiding this comment.
This comment is misleading. This being a sequence has nothing to do with the driver sending appropriate EnableDeviceType commands.
| command is sent before each application-extended command, so the gear | ||
| answers. The returned values are plain integers (or None where the gear | ||
| reports MASK or does not answer); the four status bytes are returned as | ||
| raw bytes so the caller can decode individual bits. |
There was a problem hiding this comment.
I think it would be more useful for the status to be decoded here and represented in EmergencyInformation.
Might it be better for EmergencyInformation to be a dataclass rather than a namedtuple so its members can be typed appropriately?
There was a problem hiding this comment.
Ah. That's not quite what I meant!
Information about what the status bits mean is already present in dali.gear.emergency — the responses are dali.command.BitmapResponse subclasses which already have attributes for each bit. (Eg. a QueryEmergencyModeResponse instance has attributes rest_mode, normal_mode, emergency_mode etc.)
Your sequence was throwing this information away by treating the responses as plain integers. I suggest you preserve the response classes in the dataclass for the sequence return value.
You need to decide what to do if any of the responses are missing or framing errors. I think the sequence should probably abort in this case rather than return a dataclass containing error responses.
|
Can you update the version of IEC 62386-202 used when writing this code in the list in the README.rst, please? |
Implements the IEC 62386-202 self-contained emergency control gear variable definitions and sequence helpers consumed by application controllers: - dali/memory/emergency.py: memory bank 208 (Table 18) with the control gear temperatures, battery charge/maintenance powers, rated duration, recharge/function-test times, and the full set of failure, mode, test and lamp counters. - dali/gear/sequences.py: QueryEmergencyInformation bundles the DT1 status and measurement queries into a single sequence (so the required ENABLE DEVICE TYPE 1 prefix is injected), and EmergencyCommand issues a single DT1 control command. - Fake gear emergency support plus tests for the bank, the information sequence and the control-command helper. Co-Authored-By: Claude Opus 4.8 <noreply@anthropic.com>
The driver sends EnableDeviceType before every application-extended command on its own, independent of whether the command is part of a sequence. Reword the docstring to state the actual benefit: bundling the queries into one transaction so nothing interleaves between them. Co-Authored-By: Claude Opus 4.8 <noreply@anthropic.com>
Represent the four DT1 status bytes as EmergencyMode, EmergencyFeatures, EmergencyFailureStatus and EmergencyStatus dataclasses with one bool field per IEC 62386-202 bit, and turn EmergencyInformation itself into a dataclass so every member is typed. Callers no longer have to know the bit layout. Co-Authored-By: Claude Opus 4.8 <noreply@anthropic.com>
Review feedback: the QueryEmergencyInformation sequence was throwing away the decoded bit attributes by flattening each response into plain integers and bespoke dataclasses. The dali.gear.emergency responses are command.BitmapResponse subclasses that already expose a named attribute per status bit, and the numeric responses already decode MASK. Keep each query's response object in EmergencyInformation so callers can read the named status bits and measurement values directly, and abort the sequence with a DALISequenceError if any query goes unanswered or returns a framing error instead of returning a dataclass full of error responses. Co-Authored-By: Claude Opus 4.8 <noreply@anthropic.com>
3847672 to
2336038
Compare
Done. Folded into the initial commit. |
Summary
Implements IEC 62386-202 self-contained emergency control-gear support: the
memory bank 208 variable definitions and the sequence helpers an application
controller needs to read emergency status and issue DT1 control commands.
What's included
dali/memory/emergency.py— memory bank 208 (Table 18): control-geartemperatures, battery charge/maintenance powers, rated duration,
recharge/function-test times, and the full set of failure, mode, test and
lamp counters (~40
MemoryValuedefinitions).dali/gear/sequences.pyQueryEmergencyInformation(address)— bundles the DT1 status andmeasurement queries into a single sequence so the required
ENABLE DEVICE TYPE 1prefix is injected correctly.EmergencyCommand(address, command_class)— issues a single DT1 controlcommand.
sequence, and the control-command helper.
Testing
pytest dali/tests/test_emergency.py dali/tests/test_memory.py→ 27 passed.Notes
Builds on the existing
dali/gear/emergency.pycommand classes already inmaster. Single commit, applies cleanly on top ofmaster.